Motor frequency setpoint

Home » Functions and parameters » Motor Control Mode » Motor frequency (Hz) - Velocity (RPM) » Motor frequency setpoint 


SmartDrive provides several ways to set up and modify the frequency setpoint.

  • The embedded HMI,
  • the SmartDrive App,
  • the analog inputs,
  • the preset speeds,
  • and the remote control from the network connection.


Set the frequency setpoint from the Clean Power VFD analog input.

Analog inputs from AI1 to AI3 can be assigned to be the frequency setpoint input. By default, the analog input AI1 is assigned to the frequency setpoint.

The software can set analog signals to be either a potentiometer input, a 4 to 20 mA input, or a 0 to 10 VDC input. By default, the analog input AI1 is set as a potentiometer input.

A +10V voltage output on the control terminal is the reference value.

From the SmartDrive app, the user can define the conversion scale from the analog signal to the frequency by defining the minimum and maximum frequencies.

Any value change on this input will be read instantaneously by the Clean Power VFD and become the reference setpoint.

The Frequency output will vary immediately from the actual speed to the new speed defined by the setpoint.

A change of the setpoint value from the analog input is displayed on the Clean Power VFD's HMI.


Information

If the motor speed does not reach the set value

Check the most common following causes:
  • The magnitude of the analog input differs from the Clean Power VFD input scale. Check the voltage across the analog input terminals.
  • The scale of the analog input is not set according to the user's application. Check the minimum and maximum frequencies assigned to the minimum and maximum analog input values.