Home » Applications » PID Control » PID Control parameters
Enable PID
You need to enable PID in the mobile app and configure the PID parameters to benefit from the Clean Power VFD's PID control.
Control loop performance
The PID control loop period is 100ms.
If you already use a PID control loop and desire to use the same parameters for the Clean Power VFD, check that your former control loop period is compatible.
If your former control loop period is much shorter than 100ms, you can't use the Kp and Ti parameters as they are; you need to evaluate new values.
Kp-PID proportional gain
It’s the proportional coefficient of the PID.
Adjustable from 0.01 to 250.00
Default setting=10
Ti-PID integral time constant
It’s the time constant of the PID.
Adjustable from 0.0 to 2000.0 (values are in seconds)
When Ti is set to zero, the integral action of the PID is disabled
Default setting=1
The integral action helps to eliminate steady-state error by accumulating past errors and adjusting the control effort accordingly. The integration time for a process PID controller is the time required for the integral action of the controller to match the control provided by the proportional action of the controller. It is important to set this time to be the same order of magnitude as the reaction time of the process being controlled. If the controller's integral action is too fast (i.e., the integration time is too short), it can cause the control loop to oscillate and result in instability.
Td-PID derivative time constant
adjustable from 0.0 to 1000.0 (values are in seconds)
Default setting=0.0
When the derivation time is set to 0, the VFD operates as a PI controller.
The derivative action of a PID controller acts as a brake or dampener on the control effort, helping to reduce overshoot and hunting by decelerating the descent of a process variable that is approaching the setpoint too rapidly.
|
If Kp, Ti, or Td is set to zero, then the related function (proportional, integral, respectively derivation) is disabled. E.g.: if Kp and Ti are set to a non-null value, and Td is set to zero, then the loop is controlled as a PI. |