Home » Maintenance » Fan replacement » Prepare the VFD for Fan replacement

ELECTRIC SHOCK HAZARD
The Clean Power VFD can be supplied by more than one electrical power source. Hazardous voltage can also remain inside the VFD after power has been disconnected due to energy stored in internal capacitors.
Before replacing a fan:
- Disconnect the main AC power supply.
- Disconnect the auxiliary DC power supply.
- Isolate any other external source capable of energizing the VFD.
- Apply the applicable lockout/tagout (LOTO) procedure.
- Verify the absence of voltage at the accessible power terminals using properly rated test equipment.
- Wait at least 5 minutes after all power sources have been disconnected to allow the internal capacitors to discharge.

The internal DC bus is not accessible to the user. Do not remove internal covers or access internal components to measure the DC bus voltage.
Step by step safe process:
1. Stop the motor using the normal stopping procedure.
2. Disconnect the main AC power supply to the Clean Power VFD.
3. Disconnect the auxiliary DC power supply.
4. Isolate any other external electrical source capable of supplying or back-feeding the VFD.
5. Apply the applicable lockout/tagout (LOTO) procedure to the energy-isolating devices.
6. Using properly rated test equipment, verify the absence of voltage at the accessible:
- line input terminals R/S/T (L1/L2/L3); and
- auxiliary DC power input terminals.
7. Wait at least 5 minutes after all electrical power sources have been disconnected to allow stored electrical energy inside the VFD to dissipate.
8. Verify that the fans have stopped completely before starting the replacement procedure.
9. Replace the fan while the Clean Power VFD following the process per your product part number.