Protection in regions following IEC

Home » Installing the VFD » Electrical Installation » Protection in regions following IEC 



Tables of fuses

VFD Model

Rated input current

(A)

VFD's

Iscc (kA)

Fuse type gG
Circuit Breaker (1)
SDB-1-2110-A, SDB-2-2150-A
235030A - 600V
GV3P25
SDB-1-2150A, SDB-2-2185-A305040A - 600VGV3P32
SDB-1-2185-A, SDB-2-2220-A
36
50
50A - 600VGV3P40
SDB-1-2220-A, SDB-1-2220-AL
4350
63A - 600V
GV3P50
SDB-1-2300-A
58
100
80A - 600V
GV3P65
SDB-1-2375-A
71100
100A - 600V
GV3P80
SDB-1-2450-A
86100
125A - 600V
GV4L115 
SDB-2-2300-A
47100
63A - 600V
GV3P50
SDB-2-2375-A
57
100
80A - 600V
GV3P65
SDB-2-2450-A
69100
100A - 600V
GV3P80
SDB-2-2550-A
83100
125A - 600V
GV4P115N

  (1) Breaker options are specified by the required protection level. They have not been type-tested by SmartD and must be verified for coordination by the installer/system integrator. 

Fuse Selection

This section details how to select and size fuses upstream of a SmartD Clean Power VFD. Proper sizing protects the supply, feeder cables, and the drive's AFE/DC bus (against inrush and faults) while avoiding nuisance trips.

Key IEC references

  • IEC 61800-5-1 Adjustable speed power drive systems — Safety requirements

  • IEC 60269 Low-voltage fuses (gG/gL, aM, aR)

  • IEC 60947-2 Low-voltage switchgear — Circuit-breakers

  • IEC 60364 Low-voltage electrical installations (cables, ADS/disconnection, PE sizing)

Inputs you need (from VFDs data):

Collect these before sizing:

  1. Rated input current of the selected Clean Power VFD at your line voltage.

  2. Prospective short-circuit current at the drive line terminals.

Tip: SmartD’s multilevel SiC topology greatly reduces input harmonic current and inrush spikes compared to conventional drives, but you must still size upstream protection per IEC and our published ratings.

Fuse types explained:

gG: Provides full-range overload and short-circuit protection. It is commonly used as a feeder/branch device.

aR (Semiconductor Fuse): Offers the fastest limitation of I2t for short-circuit protection.

Warning: aR fuses are for short-circuit protection ONLY. They will not protect against overloads. If you select an aR fuse, you must coordinate it with a separate overload device (like an MCCB or electronic overload).


gG fuse:

Calculate the Gg fuse ratings based on standard IEC and industry guidelines for selecting fuse protection for VFDs. Here's how to determine the ratings:

Step-by-Step Calculation:

  • Identify the rated input current of the VFD:  Example: 36 A
  • Apply the recommended IEC fuse sizing factor:

IEC and general industry practice typically recommend sizing a fuse between 125% to 150% of the VFD input current.

This factor ensures protection against short circuits and avoids nuisance trips during normal VFD operation and inrush currents.

  • Check that the selected fuse has a breaking capacity ≥ Isc at the installation point (often 50…120 kA as marked on the fuse).
  • Calculate preliminary fuse rating:

For example, at 36 A rated current: Minimum fuse size = 36 A × 1.25 = 45 A, and  Maximum fuse size = 36 A × 1.50 = 54 A

  • Select a commercially available fuse size (IEC Gg type) from standardized values:

IEC standard fuse sizes typically follow these increments:

16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160 A, etc.

From the calculated range (45–54 A), select the nearest standardized fuse size, typically rounding upwards:

In this example: 50 A.

aR fuse:

Select a fuse with In(aR) ≈ 1.25 × Irated of the Clean Power VFD (never below Irated)

If your plant has frequent brownouts/restarts or large bus capacitance banks, you may need up to ~1.6 × Irated to ride through pre-charge without nuisance fuse operation

Ensure fuse breaking capacity ≥ Isc (many aR are 80–120 kA at 400–500 V)

Important: aR fuses alone are NOT acceptable as the sole protective device (no overload protection). For fuse-only installations, use gG type. Add a close-coupled aR fuse in series with the gG only if:

  • Enhanced semiconductor protection is required, AND
  • You can demonstrate proper selective coordination between both fuses

Choosing an upstream circuit breaker (IEC 60947-2)

Thermal (overload) setting: set Ith ≈ 1.05…1.2 × Irated.

Instantaneous (magnetic) pickup: VFDs need headroom for DC bus inrush. Adjustable-magnetic MCCBs: set 8…12 × Irated  as a typical starting point (tune to site behavior).

Breaking capacity: must be ≥ Isc at the point of installation.

Instead of a thermal-magnetic breaker, you can use a magnetic-only circuit breaker (instantaneous trip only) upstream of a Clean Power VFD as the short-circuit protective device (SCPD), but you must cover overload somewhere else (another upstream thermal device)