Home » Functions and parameters » Motor Control Mode » Motor torque (%) » Speed limits in torque control mode
In torque control mode, the user must define the speed limits for which the motor should not exceed while attempting to reach the desired torque:
- Min Speed Limit in Torque Control Mode
- Max Speed Limit in Torque Control Mode
![]() | These limits are different from the motor min and max frequency in the motor parameters. However, the speed limits in torque control cannot exceed the max frequency as described in the parameter settings below. |
In torque control mode, the VFD is designed to maintain a constant torque, regardless of the speed of the motor. However, the speed limits set for the motor must also be respected for safety and longevity.
- If the speed reaches the high limit, the VFD stops increasing the supplied frequency while continuing to regulate torque as per the setpoint.
- If the speed reaches the low limit, the VFD stops decreasing the supplied frequency while still maintaining the torque setpoint.
Parameters setting:
| Parameter | Setting range | Default value | Dependencies |
|---|---|---|---|
| Min Speed Limit in Torque Control Mode | -rpm_limit to +rpm_limit RPM where rpm_limit = max_frequency_hz * nominal_velocity_rpm / nominal_frequency_hz | -nominal_velocity_rpm RPM (signed as per counter-clockwise rotation direction) | This value can not be higher than the Max Speed limit defined by motor nameplate |
| Max Speed Limit in Torque Control Mode | -rpm_limit to +rpm_limit RPM where rpm_limit = max_frequency_hz * nominal_velocity_rpm / nominal_frequency_hz | +nominal_velocity_rpm RPM | This value can not be lower than the minimum speed limit defined by motor nameplate |