Home » List and Details of alarms and protections » Analog input loss (Code: 55, 56, and 57)
This alarm applies to each of the 3 analog inputs that are configured.
Trigger condition:
This alarm arises if the analog input is configured for a 4..20 mA input signal and the current value falls under 3 mA for a duration longer than the triggering time delay
Reset condition:
The alarm resets when the signal returns to a value equal to or greater than 4mA for a duration longer than the user-defined reset delay.
Delay on triggering:
The time delay for alarm triggering is settable from 0.00s to 10.00s / default value = 0.15s
Delay on reset:
The time delay for alarm reset is settable from 0.00s to 10.00s / default value = 0.05s
Reminder — Automatic Restart:
If you want the drive to restart automatically when a Medium or Major fault/alarm clears itself, you must enable Automatic Restart. Otherwise, the drive stays stopped until you reset it and issue a new run command.