Damper control

Home » Applications » HVAC » Damper control 


HVAC Fan & Damper Control

The Clean Power VFD provides natively a simple fan and damper control logic using its embedded I/Os. It is available in version 2025.04.00 and later.

In HVAC systems, damper integration with VFDs is a common approach to achieve precise control of airflow and maintain energy efficiency. This setup typically involves VFDs controlling fan motors while dampers regulate the airflow within ductwork, allowing the system to adjust to fluctuating heating, cooling, and ventilation demands.

This combination of VFD and damper integration in HVAC is a widely adopted strategy for reducing operating costs, enhancing control, and improving the overall sustainability of building systems.


The native fan and damper control is automatically enabled when one of the VFD's digital inputs is configured for damper limit switch feedback and one relay for damper control.

  • One relay: It is recommended to use the normally closed contact of R1, as this ensures the damper remains closed by default. When R1 is energized, the damper opens; when de-energized, it returns to the closed position..
  • One digital input (DI) for the damper limit switch feedback (providing the damper open/close state).
  • One digital input (DI) for start/stop motor.

Fan and damper start sequence:

  1. The fan command is wired directly into one of the VFD’s digital inputs. The digital input indicates a start fan command.
  2. The VFD controls the configured relay (R1), which energizes to open the damper.
  3. The damper limit switch is wired back to another VFD’s digital input, indicating that the damper is in the proper position, and it is safe to start the fan.
  4. Upon receiving the damper open indication, the VFD increases the fan speed to the configured setpoint. 

 Fan and damper stop sequence:

  1. The fan command digital input indicates a stop fan command.
  2. The VFD decelerates and stops the fan.
  3. Once the fan is stopped, the VFD de-energizes the configured relay to close the damper.
  4. The damper limit switch indicates that the damper is closed.

  The native fan and damper control also includes three (3) new alarms, Please refer to the Damper control alarms section for more details.