Home » Applications » HVAC » Damper control » Damper control alarms
Native fan and damper control alarms
To ensure safe operation, three (3) new alarms have been added for the native function "fan and damper control."
- Damper open timeout
- Damper close timeout
- The damper is closed while the fan is running
Critical alarm: Damper open timeout alarm
External start feedback timeout (Code: 70).
After energizing the configured relay to open the damper, the Clean Power VFD starts a timer, ensuring the damper is opened before starting the fan.
If the damper limit switch does not indicate that the damper is opened before the configured damper open timeout, the Clean Power VFD generates a critical alarm.
It is recommended to investigate the possible causes and resolve the issue before resetting the Clean Power VFD to restore normal operation.
Medium alarm: Damper close timeout alarm
External post stop feedback timeout (Code: 71).
After stopping the fan, the Clean Power VFD de-energizes the configured relay to close the damper and starts a timer, ensuring the damper is properly closed.
If the damper limit switch does not indicate that the damper is closed before the configured damper close timeout, the Clean Power VFD generates a medium alarm.
It is recommended to investigate the possible causes and fix the problem.
These timeouts could be configured in the Advanced configuration alarms section

Critical alarm: The Damper is closed while the fan is running
While the controlled fan is running and the damper limit switch indicates the damper is closed or a damper feedback signal is lost, the Clean Power VFD generates a critical alarm and stops the fan in freewheeling to avoid high or low pressure in the duct.
It is recommended to investigate the possible causes and resolve the issue before resetting the Clean Power VFD to restore normal operation.
Reminder — Automatic Restart:
If you want the drive to restart automatically when a Medium or Major fault/alarm clears itself, you must enable Automatic Restart. Otherwise, the drive stays stopped until you reset it and issue a new run command.