Home » List and Details of alarms and protections » External alarm (Code: 74 to 77)
Overview
The External Alarm, also referred to as the User-Defined Alarm, is a flexible alarm feature that allows Clean Power VFD users to trigger internal VFD alarms based on events occurring outside the drive. It enables external devices, such as safety systems, controllers, or sensors, to initiate specific alarm behaviors on the VFD.
This capability enables integrators and administrators to utilize the drive's built-in alarm and logging systems, ensuring that the drive responds appropriately to external conditions and provides a consistent and traceable alarm history in the audit logs.
Purpose
- Integrate external fault or status signals into the VFD alarm system.
- Trigger predefined alarm actions inside the VFD from user-configured digital inputs.
Key Features
- Supports up to 4 user-defined alarms.
- Supports user-defined names up to 255 UTF-8 characters.
- Each alarm is associated with a unique code, name, severity, and predefined action.
- Alarms are logged in the audit log.
- On boot, the alarm state either persists from the previous session or starts as disabled.
- Configurable trigger and reset delay.
- Triggered by digital inputs.
Available Alarms
| Alarm Code | Name | Severity | Action (Default) | Logged |
|---|---|---|---|---|
| 74 | Ext. Critical Alarm | Critical | Freewheel + Lockout | Yes |
| 75 | Ext. Major Alarm | Major | Freewheel | Yes |
| 76 | Ext. Medium Alarm | Medium | Ramp-down to stop | Yes |
| 77 | Ext. Minor Alarm | Minor | No action | Yes |
Configuration Parameters
| Parameter | Editable | Description | Range / Values | Default |
|---|---|---|---|---|
| Enable | Yes | Enables or disables the external alarm | Enable / Disable | Disable |
| Trigger Delay | Yes | Delay before the alarm is triggered | 0.0s to 120.0s | 0.2s |
| Reset Delay | Yes | Delay before the alarm is reset after the source is cleared | 0.0s to 120.0s | 0.2s |
| Boot State | Yes | On boot, the alarm state either persists from the previous session or starts as disabled. | Enable / Disable | Disable |
| User defined name | Yes | User-defined alarm name | Up to 255 characters | - |
Input Source and Activation Rules
Alarms are triggered by configured digital inputs. Only inputs explicitly assigned to the alarm can activate it.
Digital inputs must be configured as state-based.
Audit Logging
Each activation and reset of a user-defined alarm is logged into the VFD audit log with a timestamp, alarm code, severity, and action performed.
Reminder — Automatic Restart:
If you want the drive to restart automatically when a Medium or Major fault/alarm clears, you must enable Automatic Restart. Otherwise, the drive stays stopped until you reset it and issue a new run command.