Home » Technical Specifications » Ratings SDB-1-2110-A
Power Supply
|
Supply Type
|
|
Wye, solidly grounded. TT and TN systems
|
|
Input Voltage
|
VAC
|
3 ~ 400 .. 480 | -15% .. +10%
|
|
Input Frequency
|
Hz
|
50 .. 60 | -5% .. +5%
|
|
Input Current
|
A
|
23
|
|
Apparent Power
|
kVA @ 480V
|
20
|
|
Prospective Line Isc (SCCR)
|
kA
|
50 (see Protection guide—USA/Canada or IEC—for required upstream protective device)
|
|
THDi Total Harmonic Distortion (current)
|
%
|
<3 % at load levels of 50% or greater
|
|
Imbalance max. of nominal phase to phase input voltage
|
%
|
-/+ 3% |
|
Power factor
|
|
near unity |
Electrical safety Characteristics
| Overvoltage category | III (OVC III) | |
| Protective Class of VFD | Class I |
Output capabilities
|
Output Voltage
|
VAC
|
up to 400 .. 480, depending on input voltage
|
|
Continuous Output Current - Normal Duty
|
A
|
22 @ 460 VAC 23 @ 400 VAC |
|
Continuous Output Current - Heavy Duty
|
A
|
17 @ 460 VAC 17 @ 400 VAC |
Max Transient Output current - Normal Duty During 60s, every 10 minutes at 50 °C (122 °F) |
A
|
25 @ 460 VAC 26 @ 400 VAC |
Max Transient Output current - Heavy Duty During 60s, every 10 minutes at 50 °C (122 °F)
|
A
|
26 @ 460 VAC 26 @ 400 VAC
|
|
Output Speed Frequency
|
Hz
|
0.1 .. 120 |
|
Nominal Switching Frequency
|
kHz
|
105 |
|
Effective Switching Frequency
|
kHz |
210 |
Indicative Motor Power*
|
Motor power - Normal Duty
|
kW
|
11 - 3 ~ 400 VAC 50/60 Hz 11 - 3 ~ 460 VAC 50/60 Hz |
|
Motor power - Normal Duty
|
hp
|
15 - 3 ~ 400 VAC 50/60 Hz
15 - 3 ~ 460 VAC 50/60 Hz |
|
Motor power - Heavy Duty
|
kW
|
7.5 - 3 ~ 400 VAC 50/60 Hz
7.5 - 3 ~ 460 VAC 50/60 Hz |
|
Motor power - Heavy Duty
|
hp
|
10 - 3 ~ 400 VAC 50/60 Hz
10 - 3 ~ 460 VAC 50/60 Hz |
* Motor power values are indicative. They vary depending on the motor type, technology, and manufacturer. The Clean Power VFD must not be selected based on the motor power rating.
The Clean Power VFD must be selected based on the motor Full Load Amperage (FLA), the load's driving force, the movement cycle, and the operating environment.
The Clean Power VFD must be chosen by skilled and experienced personnel.
Efficiency
|
IE Class
|
|
2
|
|
Efficiency
|
%
|
96 |