Home » Technical Specifications » Ratings SDB-2-2150-A
Power Supply
|
Supply Type
|
|
Wye, solidly grounded. TT and TN systems
|
|
Input Voltage
|
VAC
|
3~ 600Y 347Δ * | -15% .. +10%
|
|
Input Frequency
|
Hz
|
50 .. 60 | -5% .. +5%
|
|
Input Current
|
A
|
23 |
|
Apparent Power
|
kVA @ 600V
|
24 |
|
Prospective Line Isc (SCCR)
|
kA
|
50 (see Protection guide—USA/Canada or IEC—for required upstream protective device) |
|
THDi Total Harmonic Distortion (current)
|
%
|
<3 % at load levels of 50% or greater
|
|
Imbalance max. of nominal phase to phase input voltage
|
%
|
-/+ 3% |
|
Power factor
|
|
near unity |
Electrical safety Characteristics
| Overvoltage category | III (OVC III) | |
| Protective Class of VFD | Class I |
Output capabilities
|
Output Voltage |
VAC |
up to 600, depending on input voltage |
| Continuous Output Current - Normal Duty |
A |
22 @ 575 VAC |
|
Continuous Output Current - Heavy Duty |
A |
17 @ 575 VAC |
|
Max Transient Output current - Normal Duty
During 60s, every 10 minutes at 50 °C (122 °F) |
A
|
25 @ 575 VAC
|
|
Max Transient Output current - Heavy Duty
During 60s, every 10 minutes at 50 °C (122 °F) |
A
|
26 @ 575 VAC
|
|
Output Speed Frequency
|
Hz
|
0.1 .. 120 |
|
Nominal Switching Frequency
|
kHz
|
105 |
|
Effective Switching Frequency
|
kHz |
210 |
Indicative Motor Power**
|
Motor power - Normal Duty
|
kW
|
15 - 3 ~ 575 VAC 50/60 Hz
|
|
Motor power - Normal Duty
|
hp
|
20 - 3 ~ 575 VAC 50/60 Hz
|
|
Motor power - Heavy Duty
|
kW
|
11 - 3 ~ 575 VAC 50/60 Hz
|
|
Motor power - Heavy Duty
|
hp
|
15 - 3 ~ 575 VAC 50/60 Hz
|
*600Y/347Δ identifies the certified electrical distribution system (600/347 V solidly grounded Wye supplied from a Delta-Wye transformer). It is not an indication that the Clean Power VFD is approved for direct connection to a 600 V Delta distribution system. Where the facility is supplied by a Delta system, an upstream transformer providing a solidly grounded Wye secondary is required.
** Motor power values are indicative. They vary depending on the motor type, technology, and manufacturer. The Clean Power VFD must not be selected based on the motor power rating.
The Clean Power VFD must be selected based on the motor Full Load Amperage (FLA), the load's driving force, the movement cycle, and the operating environment.
The Clean Power VFD must be chosen by skilled and experienced personnel.
Efficiency
|
IE Class
|
|
2
|
|
Efficiency
|
%
|
96 |