Ratings SDB-2-2375-A

Home » Technical Specifications » Ratings SDB-2-2375-A 


Power Supply

Supply Type

Wye, solidly grounded. TT and TN systems
Input Voltage
VAC
3~ 600Y 347Δ * | -15% .. +10%
Input Frequency
Hz
50 .. 60 | -5% .. +5%
Input Current
A
57
Apparent Power
kVA @ 600V
60
Prospective Line Isc (SCCR)
kA
100 (see Protection guide—USA/Canada or IEC—for required upstream protective device)
THDi Total Harmonic Distortion (current) 
%
<3 % at load levels of 50% or greater
Imbalance max. of nominal phase to phase input voltage
%
-/+ 3%
Power factor

near unity

Electrical safety Characteristics

Overvoltage category

III (OVC III)
Protective Class of VFD
 Class I

Output capabilities

Output Voltage
VAC
up to 600, depending on input voltage
Continuous Output Current - Normal Duty
A

54 @ 575 VAC

Continuous Output Current - Heavy Duty
A
44 @ 575 VAC
Max Transient Output current - Normal Duty
During 60s, every 10 minutes at 50 °C (122 °F)
A
60 @ 575 VAC
Max Transient Output current - Heavy Duty
During 60s, every 10 minutes at 50 °C (122 °F)
A
66 @ 575 VAC
Output Speed Frequency
Hz
0.1 .. 120
Nominal Switching Frequency
kHz
105
Effective Switching Frequency
kHz
210

Indicative Motor Power**

Motor power - Normal Duty
kW
37.5 - 3 ~ 575 VAC 50/60 Hz
Motor power - Normal Duty
hp
50 - 3 ~ 575 VAC 50/60 Hz
Motor power - Heavy Duty
kW
30 - 3 ~ 575 VAC 50/60 Hz
Motor power - Heavy Duty
hp
40 - 3 ~ 575 VAC 50/60 Hz

*600Y/347Δ identifies the certified electrical distribution system (600/347 V solidly grounded Wye supplied from a Delta-Wye transformer). It is not an indication that the Clean Power VFD is approved for direct connection to a 600 V Delta distribution system. Where the facility is supplied by a Delta system, an upstream transformer providing a solidly grounded Wye secondary is required. 

** Motor power values are indicative. They vary depending on the motor type, technology, and manufacturer. The Clean Power VFD must not be selected based on the motor power rating.
The Clean Power VFD must be selected based on the motor Full Load Amperage (FLA), the load's driving force, the movement cycle, and the operating environment.
The Clean Power VFD must be chosen by skilled and experienced personnel.

Efficiency

IE Class

2
Efficiency
%
96