Low Speed Torque Compensation

Home » Functions and parameters » Motor Control Mode » V/f » Low Speed Torque Compensation 


With conventional V/F operating mode, when F (frequency) is changed, V (output voltage) is changed in the constant ratio (V/F) as shown in the figure below.

For this reason, this system is called V/F control.

The valid voltage value decreases due to a voltage drop in the wiring or the primary coil of a motor, and a sufficient amount of torque cannot be output.

The load inertia may also require greater torque to start moving.

The slower the speed is, the more prevalent this phenomenon is.

Boosting the voltage inversely proportional to the speed during ramp-up ensures good low-speed torque, and helps the motor start difficult loads more reliably.

Users can set higher voltage (torque boost ) as indicated with the solid line in the figure below to cover the shortage of torque at low speeds.

Setting the torque boost value must be done cautiously and tested in small increments.

If torque boost is increased too much or applied for too long a time, some excessive current may be drawn triggering overcurrent protection.

Setting the starting torque boost

To adapt the starting torque boost to the application, the user can define its amount and its duration.

Amount of starting boost

Parameter amount of starting boost

Settable from 0% to 30% of nominal operating voltage.

Increments: 0.1%

Default value: 0%

Starting torque boost cut-off frequency

Parameter starting torque boost cut-off frequency

Settable from 20 to 80% of nominal speed.

Default value: 25% (boost stops when the speed reaches this value)