Home » Functions and parameters » Motor Control Mode » Motor torque (%) » Torque setpoint
The torque setpoint is specified as a percentage of the motor’s rated torque, with a user-adjustable range from −500% to +500%.
SmartDrive provides several ways to set up and modify the torque setpoint.
- The embedded HMI,
- the SmartDrive App,
- the analog inputs,
- and the remote control from the network connection.
Set the torque setpoint from the Clean Power VFD analog input.
Analog inputs from AI1 to AI3 can be assigned to be the torque setpoint input. By default, the analog input AI2 is assigned to the torque setpoint.
The software can set analog signals to be either a potentiometer input, a 4 to 20 mA input, or a 0 to 10 VDC input. By default, the analog input AI2 is set as a potentiometer input.
A +10V voltage output on the control terminal is the reference value.
From the SmartDrive app, the user can define the conversion scale from the analog signal to the torque by defining the minimum and maximum torques.
Any value change on this input will be read instantaneously by the Clean Power VFD and become the reference setpoint.
The torque output will vary from the actual torque to the new torque defined by the setpoint through the user defined torque ramps.
A change of the setpoint value from the analog input is displayed on the Clean Power VFD's HMI.
|
|
If the motor torque does not reach the set value Check the most common following causes:
|