Alarms Severity

Home » Alarms and Protections » Alarms Severity 


The Clean Power VFD manages its alarms on 4 levels of severity.

To catch the user's attention, the alarm displays different colors depending on the severity level.

Severity

Purpose

Default Action

Minor

A transitory fault with little impact on the drive and the process (such as a transient voltage drop).

The motor does not stop.

The fault is reset automatically when the cause disappears and does not need any acknowledgment.

Medium

The application can generate a fault or a non-destructive electrical fault ( such as a missing phase).

These are faults that may disappear without the need for human intervention.

The motor stops when the fault occurs and lasts longer than the filter timer if one is configured.

The user configures restart behavior during setup:

- Automatic restart, or

- Manual Restart with acknowledgment.

Automatic Re-Start:

The Clean Power VFD will attempt 4 times to detect whether the fault has been cleared, with each attempt separated by a time delay.

If the fault is still present, the drive elevates the event to a critical failure. If not, the drive restarts.

Manual Re-Start with Acknowledge:

The drive will restart only with a reset (acknowledgment) of the fault. To use this mode, the user must have configured the way to trigger the acknowledgment.

If the fault has been cleared, the drive goes into a ready-to-run state, and the motor can be re-started.

If the fault is still present, the drive goes to the standby position.

Major

This can be a fault from the drive or an external fault (such as a loss of a Torque Deactivation channel).

The generated fault could be destructive and/or dangerous to human beings.

This is an abnormal situation with imminent danger risk

Example: one Torque Deactivation channel is missing (mostly coming from a disconnected wire)

The user must analyze and fix the issue.

When fixed the VFD goes into the ready-to-run state, and the motor can be restarted.

Critical

This can be a fault from the drive or an external fault (such as a short circuit).

The generated fault can be immediately destructive.

This is a hazardous condition.

The fault cannot be reset automatically.

The user must identify and fix the issue.

The drive restarts if the fault is cleared, and after a full reset from the user (a power off / power on cycle is the default reset operation for a critical fault).

Reminder — Automatic Restart:

If you want the drive to restart automatically when a Medium or Major fault/alarm clears itself, you must enable Automatic Restart. Otherwise, the drive stays stopped until you reset it and issue a new run command.