In 2 wires mode, the basic controls are run forward and run reverse.
- Run forward (default: Di3 input)
- Run reverse (default: Di4 input)
When the digital I/O control source is active:
activating Run Forward commands the motor to run forward;
activating Run Reverse commands the motor to run in reverse;
if neither input is active, the VFD stops the motor.
Unlike 3-wire control, the Run command is maintained. The motor remains commanded to run for as long as the corresponding Run input remains active.
Simultaneous activation of run forward and run reverse is managed depending user setting for the priority of spinning direction.
A digital input is managed as active upon its steady state.
A filter (acting as a delay) of fixed 20ms is enabled on the digital inputs to prevent false triggering of the control.
Unlike 3-wire control, the Run command is maintained. The motor remains commanded to run for as long as the corresponding Run input remains active.
Simultaneous activation of Run Forward and Run Reverse is managed according to the configured Spinning Direction Priority.
A digital input is processed according to its steady state.
A fixed 20 ms filter is applied to the digital inputs to prevent false triggering.
IMPORTANT: As with 3-wire control, the Run Forward and Run Reverse digital inputs control the motor only when the digital I/O source is the active control source. When Local control or another Remote control source is active, these digital-input commands do not control the motor.
HMI Stop button in 2-wire control
Because the Run command remains active in 2-wire control, pressing the HMI Stop button while an external Run command remains present requires specific behavior.
The HMI Stop Mode parameter defines whether the HMI Stop command is:
Momentary — the motor remains stopped only while the HMI Stop button is held; or
Latched — a momentary press stops the motor and prevents the existing Run command from restarting it until the Run command is re-armed.
Refer to HMI Stop Mode for complete information about the HMI Stop button behavior in 2-wire control.