Home » Functions and parameters » Motor Control Mode » General » Stopping the motor » Configure the HMI Stop mode in 2-wire control

UNEXPECTED STARTUP:
In Momentary mode, the motor can restart immediately when the HMI Stop button is released if the RUN command remains active.
Before releasing the Stop button, verify that personnel and equipment are clear of moving machinery.
NOT A SAFETY FUNCTION:
The HMI Stop button and the Stop commands described in this topic are operational control functions. They do not replace an emergency-stop circuit, Safe Torque Off (STO), or an energy-isolation procedure.
The behavior of a Stop command depends on both the control mode and the active control source.
Two situations must be distinguished:
In 2-wire control mode, the HMI Stop Mode parameter determines how the HMI Stop button behaves while a maintained RUN command remains active.
In 3-wire control mode, a Stop command assigned to a digital input is accepted only when the corresponding I/O control source is active.
The active command source is determined by the Control Source configuration.
Control source and Stop commands
The Clean Power VFD accepts operational commands from the currently selected control source.
This is particularly important when using a 3-wire Start/Stop circuit.
For example, consider a VFD configured as follows:
The digital inputs are configured for 3-wire control.
A digital input is assigned to the Stop function.
The physical Stop pushbutton is wired to this digital input.
The active control source is set to Local.
In this condition, pressing the wired Stop pushbutton does not stop the motor because the digital-input control source is not active.
Changing the physical state of the Stop input does not override the active control-source selection.
To use the wired 3-wire Start/Stop controls, select the control source associated with these digital inputs.
Example
A machine has Start and Stop pushbuttons connected to the VFD digital inputs using the 3-wire preset configuration.
The operator switches the VFD to Local control and starts the motor from the local interface.
If the operator then presses the wired Stop pushbutton:
The Stop digital input changes state.
The VFD detects the input state, but the wired I/O source is not the active command source.
The Stop command from that source is therefore not acted upon.
The motor continues to operate until a valid Stop command is received from the active control source or another applicable stopping function is activated.
HMI Stop Mode
The HMI Stop mode configuration can be found in the Motor Control / Advanced Parameters.
The HMI Stop Mode parameter applies only when the VFD is operating in 2-wire control mode.
In 2-wire control mode, the RUN command is maintained: the motor is commanded to run for as long as the RUN input remains active.
The HMI Stop Mode parameter defines what happens after the operator presses the Stop button on the HMI while the RUN command remains active.
Two behaviors are available:
- Momentary: The motor remains stopped only while the HMI Stop button is held.
- Latched: A momentary press stops the motor and prevents it from restarting until the RUN command is re-armed.
This parameter applies only when the VFD is operating in 2-wire control mode.
HMI Stop Mode parameter
| Property | Value |
|---|---|
| Parameter name | HMI Stop Mode |
| Type | Selection |
| Available values | Momentary; Latched |
| Default value | Latched* |
| Dependency | Applies only in 2-wire control mode |
| Function | Defines whether an HMI Stop command is momentary or remains latched until the RUN command is re-armed |
* The default setting is Latched. However, for VFDs operating on firmware versions prior to 2026.15, the default remains Momentary to maintain backward compatibility for upgraded units.
Momentary mode
Select Momentary when the motor must remain stopped only while the operator presses and holds the HMI Stop button.
When the HMI Stop button is pressed:
- The VFD stops the motor using the configured stop method.
- The motor remains stopped for as long as the button is held.
When the HMI Stop button is released:
- If the RUN command is still active, the VFD restarts the motor in the commanded direction.
- If the RUN command is inactive, the VFD remains stopped.
The HMI Stop command takes priority while the button is pressed, regardless of the current RUN state.
Example
A maintained digital input is commanding the motor to run.
- The operator presses and holds the HMI Stop button.
- The VFD stops the motor.
- The external RUN input remains active.
- The operator releases the HMI Stop button.
- The VFD restarts the motor automatically.
Latched mode
Select Latched when a single press of the HMI Stop button must stop the motor and prevent an already-active RUN command from restarting it.
A momentary press is sufficient. The operator does not need to hold the Stop button.
When the HMI Stop button is pressed while RUN is active:
- The VFD sets the HMI-Stop latch.
- The VFD stops the motor using the configured stop method.
- The latch remains active after the Stop button is released.
- The VFD remains stopped even if the RUN command remains continuously active.
A maintained RUN command does not clear the latch.
NOTE: Latched mode prevents a continuously active RUN command from immediately restarting the motor. It does not prevent a subsequent RUN command from starting the motor after the RUN signal has been re-armed.
Re-arm the RUN command
To clear the HMI-Stop latch and restart the motor:
- Set the RUN command to inactive.
- Set the RUN command to active again.
The transition from inactive to active creates a new RUN rising edge. If all other start conditions are satisfied, the VFD starts the motor in the commanded direction.
If the RUN command becomes inactive while the HMI-Stop latch is set:
- The latch is cleared immediately.
- The VFD remains stopped.
- The next RUN rising edge starts the motor normally, provided that all start conditions are satisfied.
Example
A maintained digital input is commanding the motor to run.
- The operator briefly presses the HMI Stop button.
- The VFD stops the motor and sets the HMI-Stop latch.
- The operator releases the Stop button.
- The external RUN input remains active, but the motor does not restart.
- The external RUN input is switched to inactive. This clears the latch.
- The external RUN input is switched back to active.
- The VFD restarts the motor if all start conditions are satisfied.
Pressing Stop while RUN is inactive
When Latched mode is selected, pressing the HMI Stop button while the following conditions are both true has no effect:
- The motor is already stopped.
- The RUN command is inactive.
No HMI-Stop latch is set, and no additional reset or re-arm action is required. The motor can start normally when the next RUN rising edge is received.
Stop method
In both Momentary and Latched modes, the VFD stops the motor according to the configured stop method.
Changing the HMI Stop Mode does not change the selected stop method.
Commissioning check
After configuring the control mode or changing the control source, verify operation from every operator control that is expected to start or stop the motor.
In particular:
Verify the selected control source.
Verify the configured 2-wire or 3-wire control mode.
Start the motor from the intended command source.
Verify that each operational Stop command associated with that source stops the motor as expected.
Change between Local and Remote control, when applicable, and confirm which Start and Stop controls remain active.
Independently verify any emergency-stop or safety-related stopping functions according to the machine safety requirements.
Audit log
Any change to the HMI Stop Mode parameter is recorded in the audit log.