Emergency Fire Mode

Home » Clean Power VFD operation » Emergency Fire Mode 



Emergency Fire Mode unavailable condition may not be signalled

Emergency Fire Mode must be available and correctly monitored before it is relied on for a fire response application.

If Emergency Fire Mode is enabled but is not available, and if the alarm relay is not configured to signal Any alarm above Minor, the unavailable condition may not be reported to the fire alarm system, building management system, or emergency response personnel.

This can create a false indication that Emergency Fire Mode is ready while the function is not available. In a fire event, this can prevent the expected fan or motor operation and can lead to smoke control failure, loss of pressurization, equipment damage, serious injury, or death.

When the system  could trigger the Emergency Fire Mode, configure the alarm relay to signal Any alarm above Minor.

Before commissioning the installation, test the Emergency Fire Mode unavailable condition and verify that the alarm is correctly signalled to the required fire safety interface and to emergency response personnel.


Overview of Emergency Fire Mode (EFM):

The Emergency Fire Mode (EFM) is an essential safety feature designed to keep critical systems operational during a fire event.

In applications where continuous operation of certain systems is critical for life safety—such as smoke extraction fans or pressurization fans—the EFM function of the Clean Power VFD enables these systems to operate under adverse conditions, even if that means bypassing typical safety protocols.

Standard VFD Operation vs. Emergency Fire Mode:

Under normal circumstances, the VFD controls the speed and torque of an electric motor by adjusting the frequency and voltage supplied to the motor. This allows for efficient control of motor performance and energy usage.

However, in the event of a fire, specific systems must continue running at full capacity to help manage smoke levels and improve visibility, potentially aiding in evacuation and rescue efforts.

When EFM is activated, the VFD temporarily overrides its usual control settings. It keeps the motor running at full speed, irrespective of any faults or abnormal conditions that might typically trigger a shutdown.

This override helps maintain essential building ventilation during a fire, supporting efforts to limit smoke spread and, in turn, enhancing life safety.

Emergency Fire Mode (EFM):

To initiate the Emergency Fire Mode, the VFD relies on an integrated response to signals from the building’s fire alarm system. The activation process follows these steps:

  1. Fire Alarm System Integration: The VFD is typically connected to the building’s fire alarm system. Upon fire alarm activation, a signal is sent directly to the VFD.
  2. Signal Interpretation: The VFD recognizes this input as a command to enter EFM mode.
  3. Mode Activation: Once the signal is received, the VFD immediately overrides its standard operation, attempting to run the connected motor at full speed.
    In this mode, the VFD disregards any faults or conditions that would normally trigger a shutdown, ensuring continuous operation of the motor.

Due to the high-stakes nature of EFM, automatic activation via the fire alarm system is usually prioritized to ensure a quick response. However, depending on specific regulations, user preferences, or system design, a manual activation option may also be included.


 Important Safety and Compliance Considerations:

While the Emergency Fire Mode provides critical operational support in fire events, it is essential to recognize that compliance with local safety regulations is the responsibility of the user or building operator, not the VFD manufacturer.

The system's design, integration, and periodic testing to ensure its proper function fall under the user's purview to maintain compliance and safety standards.


Configuration:

EFM can be activated and deactivated  by a digital input.

The user can configure the emergency fire mode action via the local HMI and mobile app.

The action options are:

1- Keep current motor operation (default action)

2- Fire mode speed and direction

  • Depending on the configured motor control mode, the user can define the emergency fire mode preset value (RPM or Hz or %).
  • The emergency fire mode preset value must be within the minimum and maximum value of the motor speed frequency or torque limits.
  • The user can define the motor direction: forward or reverse if the “allow reverse” configuration parameter is enabled.

3- Coast to stop

When the PID function is enabled, the user must define the emergency fire mode PID setpoint (default value: 0).

Audit logs:

The emergency fire mode action changes are logged in the audit log.

Dependencies:

If the “allow reverse” is disabled in the motor controls, the user can not select the option " Fire mode speed and direction".

If the “bump-less change of direction” is disabled in motor controls, the user can not select the option " Fire mode speed and direction".

Operation:

When the emergency fire mode is activated, the VFD changes to the emergency fire mode state.

In the emergency fire mode state:

  • The VFD ignores all alarms (no alarms are raised and logged) except critical and hardware alarms.
  • The VFD ignores all commands from the remote control source (except the DI assigned for emergency fire mode)
  • The VFD ignores all commands from the local control (HMI and mobile app) including STOP.
  • The VFD executes the configured emergency fire mode action.
  • The mobile app and local HMI display the emergency fire mode state
  • The HMI LED IS blinking red.

Once the emergency fire condition is cleared and the emergency fire mode is deactivated, the VFD exits the emergency fire mode and goes back to normal operation.