Home » Functions and parameters » Motor Control Mode » General » Interlock (Motor Disable)
Incorrect interlock input logic can leave the outputs powered
For an interlock function, configure the input as negative logic.
If the input logic is configured incorrectly, the system can appear to be disabled while the outputs remain powered. This can create a false sense of safety and can lead to unexpected motor operation, electric shock, mechanical movement, serious injury, or death.
Before operating the equipment, verify that the interlock input state correctly disables the system and that the outputs are not powered when the interlock is active.
Do not rely on a incorrectly configured interlock input to make the equipment safe. Use the required safety function, isolation device, or lockout/tagout procedure before working on the machine.
If the interlock is released while the RUN command is active in 2-wire mode, the VFD will start the motor immediately.
The Interlock (Motor Disable) function prevents the motor from starting and forces a stop as per the normal stop setting if asserted while the motor is running.
It is intended for external permissives (e.g., safety gates, process interlocks, lock-out/tag-out procedures) that must inhibit motion regardless of the current control source.
Configuration
- You can assign a Digital Input (DI) to the Interlock (Motor Disable) function.
- Default state: Interlock disabled (motor control enabled).
Operation
When the assigned DI becomes active (Interlock asserted), the VFD behaves as follows:
- If the motor is running, it performs the user-set normal stop immediately.
- It blocks any start/run command (the other actions: direction change, speed/torque reference will be accepted and taken into account the next time the VFD will start (once the interlock is lifted)) as long as the Interlock remains active.
- This applies in all control modes (Local HMI, Mobile App, I/O control, Network control).
Interaction & Priority
-
Emergency Fire Mode
If Emergency Fire Mode is triggered, the VFD ignores the Interlock state and executes the configured Emergency Fire action. -
Maintenance Mode
If Maintenance Mode is enabled, Interlock has higher priority. The VFD does NOT start the motor when the Interlock is active. -
Auto-Restart (after trip or power loss)
Auto-Restart does NOT start the motor solely because the Interlock is released. The motor remains stopped until a new valid start is issued. -
Alarm/Warning Actions that would start the motor
Any alarm or medium-level action configured to start/enable the motor does NOT result in a start while Interlock is active. The motor remains disabled.
Audit Log & Diagnostics
-
Event Logging
Changes of the Interlock state are recorded in the Audit Log:- Interlock Enabled (DI active) — timestamped
- Interlock Disabled (DI inactive) — timestamped
-
Status/Indication
- The HMI shows Motor Disabled by Interlock in the banner status area.
- The state of the motor (disabled) can be seen in Modbus or BACnet