Stopping the motor

Home » Functions and parameters » Motor Control Mode » General » Stopping the motor 


When the motor is in running status, it can be stopped by receiving a normal stop command.

The normal stop command is not a stop driven by the torque deactivation function, nor a stop commanded by an alarm action.

The normal stop command can come from:

  • a digital I/O that has been configured to do so, or by the absence of a run command in the 2-wires configuration of the I/O
  • an action on the stop button of the HMI
  • an action on the stop button of the mobile app
  • A stop command received from the communication media

While configuring the VFD, the user can define how the VFD stops the motor when the normal stop command is received. This is a configuration made with the mobile App that can not be changed when the VFD is in operation.

Choices are:

  • Ramp down

  • Freewheel

Ramp Down

Purpose: Ramp down involves gradually reducing the motor speed over a set time. This is done by decreasing the frequency and voltage supplied to the motor in a controlled manner.

Typical Applications:

  • Conveyor Systems: To prevent material spillage or damage by allowing conveyors to come to a smooth and controlled stop.

  • Centrifugal Pumps and Fans: To avoid water hammer in pumps and to reduce stress on fans and blowers.

  • General Industrial Machinery: To ensure a smooth and controlled deceleration of equipment, minimizing mechanical stress.

Freewheel (Coasting)

Purpose: Freewheel or coasting stop simply removes power from the motor, allowing it to slow down and stop on its own due to friction and load inertia.

Applications:

  • Emergency Stop Situations: When an immediate power cut is required without considering the deceleration profile.

  • Low-Inertia Loads: Applications where the load naturally comes to a stop quickly without additional braking effort.

  • Safety Systems: When safety systems dictate that power should be removed immediately.