2-wires, 3-wires, preset I/Os assignment

Home » Functions and parameters » Inputs and outputs » I/O's preset configuration » 2-wires, 3-wires, preset I/Os assignment 


The following sections explain the two primary methods for wiring the VFD control inputs and outputs, commonly referred to as 2-wire and 3-wire configurations.

These two options provide flexibility in how the VFD is controlled, whether using a maintained contact, such as a PLC output, or separate momentary pushbuttons, such as a dedicated Start/Stop station.

The following sections describe each control mode, the default I/O assignments, and their operation.


IMPORTANT — CONTROL SOURCE

The Start, Stop, and Direction commands assigned to the digital inputs are control commands from the digital I/O control source.

These commands control the motor only when the corresponding I/O source is the active control source.

For example, if the VFD is operating in Local control, a Start or Stop command received from a digital input does not control the motor. This is particularly important in 3-wire control, where a physically wired Stop pushbutton does not stop the motor while Local control is active.

Refer to Control Source for information about Local and Remote control-source selection.

NOT A SAFETY FUNCTION

The Start and Stop commands described in this topic are operational control functions. They do not replace an emergency-stop circuit, Safe Torque Off (STO), or an energy-isolation procedure.


2-wire, 3-wire, preset I/O assignment

There are 2 wiring presets with their configuration selectable by the user, via the mobile application:

  • 2-wires mode
  • 3-wires mode.

“2-wire” and “3-wire”  refer to two different ways you can wire the start/stop control (and sometimes forward/reverse) inputs for the drive.

  • 2-wire control is typically used with maintained contacts, such as PLC outputs or selector switches.

  • 3-wire control is typically used with separate momentary Start and Stop pushbuttons.

The preset configuration is editable by the user during the configuration phase of the VFD.

The default preset is the 3-wire configuration.

The following drawings show the I/O's that are used in the default presets with their function assignment. Those drawings are not wiring diagrams.


Wiring presets are available for speed control mode and torque control mode, with some slight differences in I/O assignment.

I/O
2- wires preset
3-wires preset

Speed control
Torque control
Speed control
Torque control
Di 3
run forward
torque applied in the forward direction
run forward
torque applied in the forward direction
Di 4
run reverse
torque applied in the reverse direction
run reversetorque applied in the reverse direction
Di5


stop
stop
Di 6
select speed reference (if a preset speed is defined)

select speed reference (if a preset speed is defined)

Ai 1
speed setpoint

speed setpoint

Ai 2

torque setpoint

torque setpoint
Relay 1
alarm output
alarm output
alarm output
alarm output
Relay 2
ready to runready to run
ready to run
ready to run
Relay 3
running
running
running
running
Aq 1
motor speed
motor torque
motor speed
motor torque
Aq 2
motor current
motor current



2-wires connection for speed control:


3-wires connection for speed control :

2-wires connection for torque control:


3-wires connection for torque control :

For operation, read the chapters:
3-wires preset- Operation

and

2-wires preset- Operation