Home » Mobile App » Authentication
Once the app is installed, the user can log in with username "admin" and password as the serial number of the CleanPower VFD
The serial number of the Clean Power VFD must be written with a hyphen, in this format: xxxx-xxxxxxxx-xxxxxx
The serial number of the Clean Power VFD is written on the device side label, which is described in the section VFD nameplate description
- Change password
- Password complexity:
- Regular login
- Notes on privacy (how the app handles your password)
- Reset the password
- Log out from mobile application
- Mobile App Background Behavior
Change password
-
Go to Menu > configuration > authentication
-
Enter a new password.
-
Save. Your next login will use these new credentials.
Password complexity:
The new password must be different from the current password
The password you create must have
Minimum length of 10 characters
Maximum length of 255 characters
Minimum 1 upper case
Minimum 1 lower case
Minimum 1 digit
Minimum 1 symbol
Maximum 2 consecutive identical characters
Maximum 3 consecutive sequential characters
and can not
Contain the word "password"
Contain your username
Regular login
To log in, provide:
-
Username
-
Password
If login fails, you’ll see: “Invalid username or password.”
Notes on privacy (how the app handles your password)
- Passwords are never stored in clear text.
- Passwords are salted and hashed, then encrypted at rest in the database.
Reset the password
For security reasons, the password cannot be reset through unsecured methods.
Access must be restored by performing a factory reset; however, this action will also erase the current system configuration.
To reset the password while preserving your configuration, please strictly follow this procedure:
From the HMI,
Export the current configuration to a USB drive.
Perform a factory reset on the device.
Import the previously exported configuration from the USB drive.
Log out from mobile application
For cybersecurity reason, when you chooses Logout, the remote endpoint immediately ends the current session.
This action closes the active connection and invalidates the session credentials, so the VFD will no longer accept requests made with the same authorization token or refresh token.
After logout, any attempt to reuse these tokens is rejected, and you must authenticate again to interact with the VFD.
Mobile App Background Behavior
The mobile application maintains active communication with the VFD when running in the background for a limited duration.
When the application is sent to the background, it continues to exchange heartbeat messages with the drive for approximately 10 minutes. This mechanism is intended to preserve the active session during short interruptions (e.g., switching apps).
After this period, communication is automatically lost and must be re-established when returning to the application.
The VFD does not implement an automatic disconnect mechanism; the session termination is driven by the mobile application behavior.