The user can assign digital inputs. The options available are as follows:

Assignment:

  • Select Speed Frequency Reference: When active, the frequency reference is determined by the configured analog input. If inactive, the frequency is set by the preset value.
  • Select Speed Velocity Reference: When active, the velocity reference is determined by the configured analog input. If inactive, the velocity is set by the preset value.
  • Activate Maintenance Mode: Set the VFD into maintenance mode
  • External Critical Alarm:  trigger an internal VFD alarm based on events occurring outside the drive 
  • External Major Alarm:  trigger an internal VFD alarm based on events occurring outside the drive  
  • External Medium Alarm:  trigger an internal VFD alarm based on events occurring outside the drive  
  • External Minor Alarm:  trigger an internal VFD alarmsbased on events occurring outside the drive  
  • Interlock: Motor-Disable function preventing the motor from starting and forces a stop 
  • Select active configuration: Switches which stored configuration controls the drive 
  • Not assigned: Not currently assigned to any specific task or function

Di1 and Di2 can also be assigned to an incremental encoder input. Read more in the dedicated chapter.

Trigger type:

The input can be set as "active" depending on the user-defined trigger.

The choices for the trigger are:

  • Not assigned: The input remains inactive whatever electrical signal happens on its terminal
  • Rising edge: The input becomes active when a transition from a low voltage (inactive state) to a high voltage (active state) is detected on its terminal. This is typically used in digital systems for edge-triggered events.
  • Falling edge: The input becomes active when a transition from a high voltage (active state) to a low voltage (inactive state) is detected on its terminal. Like the rising edge, this is used for edge-triggered events.
  • High: The input is considered active when a high voltage is detected on its terminal. This is typically used in systems that operate on level-triggered events.
  • Low: The input is considered active when a low voltage is detected on its terminal. This is also used in systems that operate on level-triggered events.

Please note that the specific levels for “high” and “low” states refer to the voltage levels for states ON and OFF, for Sink and Source connection logic, as defined in the digital input specifications chapter.

Debounce delay:

A debounce delay can be set to prevent rapid fluctuations in input signals from causing erratic behavior in the motor control.

It ensures that the VFD only responds to sustained changes in input, rather than temporary fluctuations